M4-M5 Link Tunnel Attenuator CFD Analysis

CFD simulation of airflow through horizontal splitter attenuator in the M4-M5 Link tunnel project, illustrating pressure loss analysis across porous splitter domains and surrounding infrastructure.

IAC Acoustics (WestConnex M4-M5 Link – Sydney, New South Wales, Australia)

IAC Acoustics required fluid flow analysis of a horizontal splitter attenuator for the M4-M5 Link tunnel project. Fluid flow analysis was performed to characterise the total pressure loss of the 3 m length parallel splitter configuration considering roof/floor, walls and offset distance from upstream concrete columns.   

What we did:

Outcome:

Avesta Consulting verified the total pressure loss for the horizontal splitter attenuator and confirmed design compliance with project specific maximum pressure loss requirements.